Rated Voltage | 12 kV |
Network Frequency Withstand Voltage 1min | 28 kV |
Clearance (Contacts) | 32 kV |
Lightning Impulse Withstand Voltage (1.2/50 µsec) | 75 kV |
Clearance | 85 kV |
Rated Frequency | 50/60 Hz |
Rated Current | 630-1250 A |
Rated Short Circuit Withstand Current (1sec)(3sec) | 16-20-25 kA |
Rated Short Circuit Closing Current | 50 kA-tepe |
Mechanical Class | M2 |
Electrical Class | E2 |
Protection Class | AFL |
Internal Arc Class | IP3X |
ARME-AIS12 YGC Load Break Switch Incoming-Outgoing Unit | Download |
ARME-AIS12 YST Fuse – Load Break Switch Transformer Protection Unit | Download |
ARME-AIS12 YAG Voltage&Current Measurement Unit with LBS | Download |
ARME-AIS12 GKC Circuit Breaker İncoming/Outgoing Unit | Download |
ARME-AIS12 GKT Circuit Breaker ,Transformer Protection Unit | Download |
ARME-AIS12 GKK Bus Coupling with Circuit Breaker Unit | |
ARME-AIS12 GAG Voltage&Current Measurement Unit with LBS | |
Please contact with our S&M team via sales@armtek.com.tr for more types |
Dosyaları Ön İzle;
General articles relating to High Voltage Switchgears | IEC 62271 |
Metal Enclosed Switchgears (1 – 52 kVac] | IEC 62271-200 |
Circuit Breakers (1 – 52 kVac] | IEC 62271-100 |
Main Circuit and Grounding Disconnectors | IEC 62271-102 |
AC Switch and Fuse Combinations | IEC 62271-105 |
Current Transformers | IEC 61869-2 |
Voltage Transformers | IEC 61869-3 |
Post Insulators | IEC 60273 |
Measuring Devices | IEC 60051 |
Secondary Protection Relays | IEC 60255 |
Live Working – Voltage Detectors | IEC 61243-1 |